3 Installation
3.6 Electrical Installation
108 DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com
3.6.2.5 Digital Input Signals
Control signal terminals 2, 3, 4, 6 and 10 all have the same function and
mode of operation as digital inputs (DI1 to DI5).
A logic level of +24 V (positive logic) is used:
8 - +30 V = High (logic "1")
0 - +4 V = Low (logic "0")
Input current:
~ 4mA
Signal common 0 V (control signal terminal 7 or 9)
The internal control voltage from control signal terminal 1 (+24 V) or an
external voltage source (+24 V) can be used for this.
By default (with the unit as supplied), the control signal terminals for the
digital input signals will be assigned as follows:
Control signal terminal 2 as digital input 1 (DI1) = FWD (clockwise
rotating field enable signal)
Control signal terminal 3 as digital input 2 (DI2) = REV (counterclockwise
rotating field enable signal)
Control signal terminal 4 as digital input 3 (DI3) = Used to switch from
f-Set to fixed frequency (f-Fix1, f-Fix2)
Control signal terminal 6 as analog input 1 (AI1) = f-Set analog setpoint
Control signal terminal 10 as digital input 5 (DI5), can be switched
between f-Fix1 and f-Fix2.
Figure 78:Control signal terminals (digital / analog)
The setting (digital/analog) for terminals 6 and 10 will be
configured automatically based on the value set for P1-13.
2
DI1
FWD
+24 V
4
DI3
Select
AI1 REF/f-Fix
3
DI2
REV
10
DI5
(AI2)
Select
f-Fix Bit 0
1
+24 V Out
< 100 mA
6
AI1
(DI4)
CPU
8
AO1
(DO1)
f-Out
0...+10 V/20 mA
AI1 REF
0...+10 V/20 mA
11
AO2
(DO2)
A-Out
0...+10 V/20 mA
7
0 V
0 V
9
0 V
0 V