6 Technical Data
6.1 General rating data
146 DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com
Control section
Terminal capacity (clampable) A mm
2
0.05 - 2.5 (30 - 12 AWG)
Control voltage
Output voltage (control signal terminal 1) U
c
V DC 24
Input voltage (control signal terminal 1) U
c
V DC 18 - 30
Load rating (control signal terminal 1), maximum I mA 100
Reference voltage (control signal terminal 5) U
S
V DC 10
Load rating (control signal terminal 5), maximum I mA 10
Digital Input (DI)
Number (configurable) 3 - 5
Logic (level) Increase
Response time t ms <4
Input voltage range High (1) U
c
V DC 8 - 30
Input voltage range Low (0) U
c
V DC 0 - 4
Analog Input (AI)
Number (configurable) 0 - 2
resolution 12 bits
accuracy % < 1 to the final value
Response time t ms <4
Input voltage range U
Ref
V 0/-10 - +10, DC (R
i
~ 72 kΩ)
Input current range I mA 0/4 - 20 (R
B
~ 500 Ω)
Setpoint potentiometer (recommended fixed resistance)
R kΩ 1 -10
Relay output (K)
Number of relays (contacts) 2 (1 N/O/1 changeover contact)
Switching capacity
AC I A 6 (250 V)
DC current I A 5 (30 V)
Digital/analog output (DO/AO)
Quantity 2 (digital/analog)
Output voltage
TH U
out
V DC +24
AO U
out
V DC 0/-10 - +10
Current carrying capacity DO I
out
mA < 20
AO resolution 12 bits
Interface (RJ45) OP bus, Modbus RTU, CANopen, (RS485)
STO (Safe Torque Off)
Voltage U V DC +24 (18 - 30)
Current I mA 100
SIL category 2
PL d
Technical data Symbol Unit Value