6 Technical Data
6.2 Specific rated operational data
DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com 149
DA1-32… series
Physical quantity Symbol Unit 030 046 061 072 090 110
Rated operational current I
e
A 30 46 61 72 90 110
Overload current for 60 s every 600 s at 50 °C i
l
A 58.5 69 91.5 108 135 165
Apparent power at rated operation 230 V S kVA 15.5 18.3 24.3 28.7 35.9 43.8
240 V S kVA 16.2 19.1 25.4 29.9 37.4 45.7
Assigned Instance Motor Power 230 V P kW 7.5 11 15 18.5 22 30
230 V P HP
10 15 20 25 30 40
Power side (primary side):
Number of phases three-phase
Rated operating voltage U
LN
V 200V -10% - 240V +10%, 50/60Hz
(180 - 264 V ±0 %, 48 - 62 Hz ±0 %)
Input current (phase current) I
LN
A 33 50 64 74 99 121
Minimum braking resistance R
B
Ω 22 22 12 12 6 6
Pulse frequency
Default settings f
PWM
kHz 8 8 8 8 8 4
Setting range f
PWM
kHz 4 - 24 4 - 24 4 - 24 4 - 24 4 -24 4 - 16
Maximum leakage current to earth (PE), without motor I
PE
mA 1.42 1.42 0.28 0.28 1.54 1.54
Efficiency η 0.97 0.97 0.97 0.97 0.97 0.97
Heat dissipation at I
e
P
V
W 187.5 264 345 518 550 720
Frame size FS4 FS4 FS5 FS5 FS6 FS6