6 Technical Data
6.2 Specific rated operational data
150 DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com
DA1-32… series
Physical quantity Symbol Unit 150 180 202 248
Rated operational current I
e
A 150 180 202 248
Overload current for 60 s every 600 s i
l
A 225 270 303 372
Apparent power at rated operation 230 V S kVA 59.8 71.7 80.5 98.8
240 V S kVA 62.4 74.8 84 103.1
Assigned Instance Motor Power 230 V P kW 37 45 55 75
230 V P HP 50 60 75 100
Power side (primary side):
Number of phases three-phase
Rated operating voltage U
LN
V 200V -10% - 240V +10%, 50/60Hz
(180 - 264 V ±0 %, 48 - 62 Hz ±0 %)
Input current (phase current) I
LN
A 160 188 207 246
Minimum braking resistance R
B
Ω 6 6 6 6
Switching frequency (pulse frequency)
Default settings f
PWM
kHz 4 4 4 4
Setting range f
PWM
kHz 4 - 12 4 - 8 4 - 16 4 - 12
Maximum leakage current to earth (PE), without motor I
PE
mA 1.54 1.54 2.74 2.74
Efficiency η 0.97 0.98 0.98 0.98
Heat dissipation at I
e
P
V
W 814 945 1100 1425
Frame size FS6 FS6 FS7 FS7