6 Technical Data
6.7 Mains chokes
174 DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com
Table 40: Assigned mains chokes – DA1 voltage class 400 V (three-phase)
Device Type Input
current
Mains choke
U
LN
max. 500 V +10%, 50/60 Hz ±10 %
I
LN
max. 40
o
C max. 50
o
C
A Type A Type A
Mains voltage: 400 V
Supply voltage (50/60 Hz) U
LN
380 (-10%) - 480 (+10 %) V
U
e
400 V AC, three-phase / U
2
400 V AC, three-phase
DA1-342D2FB-… 3.5 DX-LN3-006 6 DX-LN3-006 6
DA1-344D1FB-… 6 DX-LN3-006 6 DX-LN3-006 6
DA1-345D8FB-… 7.5 DX-LN3-010 10 DX-LN3-010 10
DA1-349D5FB-… 12 DX-LN3-016 16 DX-LN3-016 16
DA1-34014FB-… 17 DX-LN3-025 25 DX-LN3-025 25
DA1-34018FB-… 22 DX-LN3-025 25 DX-LN3-025 25
DA1-34024FB-… 28 DX-LN3-040 40 DX-LN3-040 40
DA1-34030FB-B55C 34 DX-LN3-040 40 DX-LN3-040 40
DA1-34039FB-B55C 44 DX-LN3-050 50 DX-LN3-050 50
DA1-34046FB-B55C 52 DX-LN3-050 50 DX-LN3-080 80
DA1-34061FB-B55C
1)
66 DX-LN3-060 60 DX-LN3-080 80
DA1-34072FB-B55C
1)
77 DX-LN3-080 80 DX-LN3-080 80
DA1-34090FB-B55C
1)
103 DX-LN3-100 100 DX-LN3-120 120
DA1-34110FB-B55C
1)
126 DX-LN3-120 120 DX-LN3-160 160
DA1-34150FB-B55C
1)
165 DX-LN3-160 160 DX-LN3-200 200
DA1-34180FB-B55C
1)
192 DX-LN3-200 200 DX-LN3-200 200
DA1-34202FB-B55C
1)
211 DX-LN3-250 250 DX-LN3-250 250
DA1-34240FB-B55C
1)
241 DX-LN3-250 250 DX-LN3-300 300
DA1-34302FB-B55C
1)
299 DX-LN3-300 300 DX-LN3-370 370
DA1-34370FB-B20C
2)
377 DX-LN3-370 370 DX-LN3-450 450
DA1-34450FB-B20C
2)
459 DX-LN3-450 450 Please enquire N/A
1) DA1 variable frequency drive with DC link choke
2) If it is not guaranteed that the system percentage impedance is greater than or equal to 1%, a mains choke
must be connected. Your u
K
value should fall between 1 and 4%.