6 Technical Data
6.7 Mains chokes
DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com 175
Table 41: Assigned mains chokes – DA1 voltage class 500 V (three-phase)
Device Type Input
current
Mains choke
U
LN
max. 500 V +10%, 50/60 Hz ±10 %
I
LN
max. 40
o
C max. 50
o
C
A Type A Type A
Mains voltage: 500 V
Supply voltage (50/60 Hz) U
LN
500 (-10%) - 600 (+10 %) V
U
e
500 V AC, three-phase / U
2
500 V AC, three-phase
DA1-352D1NB-… 3.5 DX-LN3-006 6 DX-LN3-006 6
DA1-353D1NB-… 4.5 DX-LN3-006 6 DX-LN3-006 6
DA1-354D1NB-… 5 DX-LN3-006 6 DX-LN3-006 6
DA1-356D5NB-… 9 DX-LN3-010 10 DX-LN3-010 10
DA1-359D0NB-… 12 DX-LN3-016 16 DX-LN3-016 16
DA1-35012NB-… 15 DX-LN3-016 16 DX-LN3-016 16
DA1-35017NB-… 21 DX-LN3-025 25 DX-LN3-025 25
DA1-35022NB-… 26 DX-LN3-025 25 DX-LN3-040 40
DA1-35028NB-B55C 33 DX-LN3-040 40 DX-LN3-040 40
DA1-35034NB-B55C 40 DX-LN3-040 40 DX-LN3-050 50
DA1-35043NB-B55C
1)
49 DX-LN3-050 50 DX-LN3-050 50
DA1-35054NB-B55C
1)
60 DX-LN3-060 60 DX-LN3-080 80
DA1-35065NB-B55C
1)
71 DX-LN3-080 80 DX-LN3-080 80
DA1-35078NB-B55C
1)
91 DX-LN3-100 100 DX-LN3-100 100
DA1-35105NB-B55C
1)
121 DX-LN3-120 120 DX-LN3-160 160
DA1-35130NB-B55C
1)
143 DX-LN3-160 160 DX-LN3-160 160
DA1-35150NB-B55C
1)
158 DX-LN3-160 160 DX-LN3-200 200
1) DA1 variable frequency drive with DC link choke
Please enquire for mains chokes for mains voltages > 500 V.
For more information and technical data on DX-LN…
mains chokes, please refer to instruction leaflet
IL00906003Z.