6 Technical Data
6.8 Radio inter ference suppression filter
DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com 177
Voltage class: 230 V
Mains voltage (50/60 Hz) ULN 200 (-10%) - 240 (+10 %) V
U
e
230 V AC, single-phase / U
2
230 V AC, three-phase
Table 42: Assigned radio interference suppression filter (single-phase)
Device Type
Frame
size
Input
current
Radio interference suppression filter U
LN
: max. 250 V +0 %, 50/60 Hz ±10 %,
maximum ambient air temperature: 50
o
C
Type Ampere
rating
Leakage
current
(IEC38 +10 %)
max. motor cable length
C1 C2 C3
I
LN
I
e
I
PE
l l l
A A A m m m
DA1-124D3FB-A20C FS2 9 DX-EMC12-014-FS2 14 8 25 50 75
DA1-127D0FB-A20C FS2 13 DX-EMC12-014-FS2 14 8 25 50 75
DA1-12011FB-A20C FS2 19 DX-EMC12-025-FS2 25 8 25 75 100
DX-EMC…-FS2: base-mounted filter for frame size FS2