1 DA1 device series
1.4 Rated operational data
DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com 17
Catalog number selection
Inscription Meaning
DA1-124D3FB-A20C DA1 = DA1 series variable frequency drive
1 = Single-phase main terminal
2 = Mains voltage category: 230 V (200 V - 240 V ±10 %)
4D3 = Rated operational current: 4.3 A
N = Internal radio interference suppression filter
B = Internal brake chopper
A = LED display
20 = IP20 degree of protection
C = PCB protection (coated board)
DA1-327D0FB-A20C
DA1 = DA1 series variable frequency drive
3 = Three-phase main terminal
2 = Mains voltage category: 230 V (200 V - 240 V ±10 %)
7D0 = Rated operational current: 7.0 A
N = Internal radio interference suppression filter
B = Internal brake chopper
A = LED display
20 = IP20 degree of protection
C = PCB protection (coated board)
DA1-34014FB-B66C
DA1 = DA1 series variable frequency drive
3 = Three-phase main terminal
4 = Mains voltage category: 400 V (380 V - 480 V ±10 %)
014 = Rated operational current: 14 A
N = Internal radio interference suppression filter
B = Internal brake chopper
B = OLED display
66 = IP66 degree of protection
C = PCB protection (coated board)
DA1-35043NB-B55C
DA1= DA1 series variable frequency drive
3 = Three-phase main terminal
5 = Mains voltage category: 575 V (500 V - 600 V ±10 %)
043 = Rated operational current: 43 A
N = No internal radio interference suppression filter
1)
B = Internal brake chopper
B = OLED display
55 = IP55 degree of protection
C = PCB protection (coated board)
1) See following note
For DA1-35…NB-… devices, an external radio interference
suppression filter is required for operation as per IEC/EN 61800-3.