1 DA1 device series
1.4 Rated operational data
22 DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com
Mains supply voltage: 3 AC 500 V, 50 Hz/575 V, 60 Hz
Output voltage: 3 AC 500 V, 50 Hz/550 - 600 V, 60 Hz
Type
Rated operational
current
Assigned motor power
(induction motor)
Display (operating
unit)
Local controls
Radio interference
suppression filter
DC link choke
Degree of
protection
Frame size
Brake chopper
I
e
P
(500 V, 50 Hz) P
1)
(550 - 600 V, 60 Hz) IP FS B = Yes
A kW HP
DA1-352D1NB-A20C 2.1 0.75 1 LED – – – IP20 FS2 B
DA1-352D1NB-B66C 2.1 0.75 1 OLED – – – IP66 FS2 B
DA1-352D1NB-B6SC 2.1 0.75 1 OLED ✓ – – IP66 FS2 B
DA1-353D1NB-A20C 3.1 1.5 2 LED – – – IP20 FS2 B
DA1-353D1NB-B66C
3.1 1.5 2 OLED – – – IP66 FS2 B
DA1-353D1NB-B6SC
3.1 1.5 2 OLED ✓ – – IP66 FS2 B
DA1-354D1NB-A20C 4.1 2.2 3 LED – – – IP20 FS2 B
DA1-354D1NB-B66C 4.1 2.2 3 OLED – – – IP66 FS2 B
DA1-354D1NB-B6SC 4.1 2.2 3 OLED ✓ – – IP66 FS2 B
DA1-356D5NB-A20C 6.5 4 5 LED – – – IP20 FS2 B
DA1-356D5NB-B66C
6.5 4 5 OLED – – – IP66 FS2 B
DA1-356D5NB-B6SC 6.5 4 5 OLED ✓ – – IP66 FS2 B
DA1-359D0NB-A20C 9 5.5 7.5 LED – – – IP20 FS2 B
DA1-359D0NB-B66C 9 5.5 7.5 OLED – – – IP66 FS2 B
DA1-359D0NB-B6SC 9 5.5 7.5 OLED ✓ – – IP66 FS2 B
DA1-35012NB-A20C 12 7.5 10 LED – – – IP20 FS3 B
DA1-35012NB-B66C 12 7.5 10 OLED – – – IP66 FS3 B
DA1-35012NB-B6SC
12 7.5 10 OLED ✓ – – IP66 FS3 B
DA1-35017NB-A20C
17 11 15 LED – – – IP20 FS3 B
DA1-35017NB-B66C 17 11 15 OLED – – – IP66 FS3 B
DA1-35017NB-B6SC 17 11 15 OLED ✓ – – IP66 FS3 B
DA1-35022NB-A20C
22 15 20 LED – – – IP20 FS3 B
DA1-35022NB-B55C
22 15 20 OLED – – – IP55 FS4 B
DA1-35028NB-B55C
28 18.5 25 OLED – – – IP55 FS4 B
DA1-35034NB-B55C 34 22 30 OLED – – – IP55 FS4 B
DA1-35043NB-B55C 43 30 40 OLED – – ✓ IP55 FS5 B
DA1-35054NB-B55C 54 37 50 OLED – – ✓ IP55 FS5 B
DA1-35065NB-B55C 65 45 60 OLED – – ✓ IP55 FS5 B
DA1-35078NB-B55C 78 55 75 OLED – – ✓ IP55 FS6 B
DA1-35105NB-B55C 105 75 100 OLED – – ✓ IP55 FS7 B
DA1-35130NB-B55C
130 90 125 OLED – – ✓ IP55 FS6 B
DA1-35150NB-B55C
150 110 150 OLED – – ✓ IP55 FS7 B
1) Quote from “Power Conversion Equipment - UL 508C, May 3, 2002”.