EasyManua.ls Logo

EG4 GRIDBOSS - Generator Operation

EG4 GRIDBOSS
74 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
27
GENERATOR OPERATION
The attached generator can only be started when the grid is lost, and the generator is wired for 2-wire
stop/start using the Dry 1” contacts on the communications board. The internal grid relay and the
internal generator relay cannot be closed at the same time to ensure generator output does not send
power to the grid.
The GridBOSS should use start/stop relay 1 in the normally open connection. Start/stop relay 1 can be
controlled manually or by battery SOC/voltage logic within the EG4
®
Monitor Center. The generator can
also be configured with warm-up, cool-down, and exercise time.
The GridBOSS generator relay can only be closed after the start/stop relay 1 is closed. When start/stop
relay 1 is closed, the GridBOSS must wait until the generator can supply stable output power. This wait
time is configured using the generator warm-up time setting in the EG4
®
Monitor Center. Once the
generator warm-up time is complete, the GridBOSS will close the generator relay. Before the generator
can be safely powered off, the generator must complete the cool-down time. Once the cool-down time
is complete, the GridBOSS will open the generator relay and start/stop relay 1. The Start/Stop relay 1
connection is labeled Dry 1 on the GridBOSS cover plate. The Dry 2 connections are currently unused
and reserved for future use.
Generator 2-Wire Start Specifications
Maximum Voltage 30VDC, 277VAC
Maximum NO Contact Current: 5A
Maximum NC Contact Current: 3A
GridBOSS Communications Board
COM1 and NC1 are a set of normally closed switches
COM1 and NO1 are a set of normally open switches
COM2 and NC2 are a set of normally closed switches
COM2 and NO2 are a set of normally open switches
NC1
COM1
NO1
NC2
COM2
NO2
Dry 1
Dry 2

Related product manuals