21
more than 10 minutes, the inverter output will be cut off.
Normal / Standby: Select Normal for the inverter to operate normally. Select Standby to
halt all power input and output.
Restart Inverter: This restarts the inverter.
Battery ECO Enable: When enabled, the inverter will switch to bypass mode if the battery
has reached the On-Grid EOD value and AC charging is disabled. The inverter will stay in
bypass mode until the battery is being charged again. Switch time can be up to 15ms.
Buzzer Enable: Enable/disable the alarm buzzer.
ISO Enable: Enable/disable PV ground fault circuit interrupter.
6.2 APPLICATION SETTING
NOTE: The user must also establish the paralleling scheme using Setting 21 in the user interface.
NoPL (Not Parallel), 1PH(Single Phase), 3PH (Three Phase). See section 11, LCD Settings for details.
EPS Voltage Set(V): Set the inverter’s output voltage.
EPS Frequency Set(Hz): Set the inverter’s output frequency.
AC Input Range: Set the voltage range for AC Input.
PV Grid Off: If the customer wants the system to have Off-Grid functionality without
installing any batteries, please enable PV Grid Off. Please note, in this situation the Off-
Grid energy is supplied by solar and is not stable. We suggest the customer install
battery/batteries to keep the inverter output voltage stable if they want to have Off-Grid
function. (Allows system to access the Off-Grid mode when only solar input is available
without battery storage). Note: It is not recommended to run the system without battery
backup.
PV Arc: Enables detection of arcs on the PV input circuits to the inverter and provides
protection from PV circuit arcs.
PV Arc Fault Clear: Clears any fault detected due to arcs on the PV input circuit to the
inverter.
RSD: Enables the Rapid Shut Down feature.
N-PE Connect (Inner): Enable for the AC Neutral (N) and AC Ground (PE) to be bonded.
AC First
AC first Start Time 1-3: The time at which the Inverter will use only AC to power loads.
The range is 00:00 to 23:59.
AC first Stop Time 1-3: The time at which the Inverter will use only AC to power loads.
The range is 00:00 to 23:59.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EG4 LuxPowerTek 6000XP and is the answer not in the manual?

EG4 LuxPowerTek 6000XP Specifications

General IconGeneral
CategoryInverter
Rated Power6000W
Max DC Input Power7800W
Number of MPPT Trackers2
Battery Voltage48V
Max Charge/Discharge Current120A
Protection DegreeIP65
Frequency50/60Hz
ModelLuxPowerTek 6000XP
CommunicationRS485
Operating Temperature Range-25°C to 60°C
Protection FeaturesOver Voltage Protection, Over Temperature Protection
CoolingFan