5.16 EXAMPLE OF DIAGRAM WITH DOUBLE BAL. INPUTS MP500/8 MP500/16
3) Example of connection with tamper on SAB input
5) Example of connection on double BAL input
6) Example of connection with alarm and tamper on double BAL input
IMPORTANT!
Each sensor must be powered by
the device that controls it. The balancing resistors must be connected to the
positive
of the power supply of the same device.
IMPORTANT!
In order to guarantee conformity to the EN50131 standard, the U2 output, tamper alarm, must be connected to the intern
al siren.
For Grade 3 use an ATS4 dialler (see
paragraph
5.12.8.1
.