Rosemount Model 8800C Vortex Flowmeter
3-4
Shedding Frequency
Shows the shedding frequency for the flow simulation.
Configure Flow Simulation
Allows you to configure your flow simulation (internal or external).
Simulate Flow Internal
The simulate flow internal function will automatically disconnect the
sensor and enable you to select the configuration of the internal
simulate (fixed or varying).
Fixed Flow
The fixed flow simulation signal can be entered in either a percent of
range or flow rate in current engineering units.
Varying Flow
The minimum and maximum flowrate can be entered in either percent
of range or as a flow rate in current engineering units. The ramp time
can be entered in seconds from a minimum of 0.533 seconds to a
maximum of 34951 seconds.
Simulate Flow External
Simulate flow external allows you to disconnect the sensor
electronically so an external frequency source can be used.
Enable Normal Flow
Enable normal flow allows you to exit the flow simulation mode
(internal or external) and return to normal operation mode.
Mode
Mode allows you to view which flow simulation mode you are in:
• Internal (flow simulation – internal)
• Snsr Offln (flow simulation – external)
• Norm Flow (normal flow operation)
HART Comm. 1, 2, 4, 2
HART Comm. 1, 2, 4, 3
HART Comm. 1, 2, 4, 3, 1
HART Comm. 1, 2, 4, 3, 1, 1
HART Comm. 1, 2, 4, 3, 1, 2
HART Comm. 1, 2, 4, 3, 2
HART Comm. 1, 2, 4, 4
HART Comm. 1, 2, 4, 5