2-35
Installation
Diagnostic Messages In addition to the output, the LCD indicator displays diagnostic
messages for troubleshooting the flowmeter. These messages
are as follows:
SELFTEST
The flowmeter is in the process of performing an electronics self test.
FAULT_ROM
The flowmeter electronics has undergone a EPROM checksum fault.
Contact your Field Service Center.
FAULT_EEROM
The flowmeter electronics has undergone a EEPROM checksum fault.
Contact your Field Service Center.
FAULT_RAM
The flowmeter electronics has undergone a RAM test fault.
Contact your Field Service Center.
FAULT_ASIC
The flowmeter electronics has undergone a digital signal processing
ASIC update fault. Contact your Field Service Center.
FAULT_CONFG
The flowmeter electronics has lost critical configuration parameters.
This message will be followed by information detailing the missing
configuration parameters. Contact your Field Service Center.
FAULT_COPRO
The flowmeter electronics has detected a fault in the math coprocessor.
Contact your Field Service Center.
FAULT_SFTWR
The flowmeter electronics has detected a non-recoverable fault in the
software operation. Contact your Field Service Center.
FAULT_BDREV
The flowmeter electronics has detected incompatible electronics
hardware. Contact your Field Service Center.
FAULT_LOOPV
The flowmeter electronics has detected insufficient voltage to power the
sensor board. Most likely the cause is low voltage at transmitter
4–20 mA terminals. Contact your Field Service Center.
FAULT_SDCOM
The flowmeter electronics has detected an unexpected sigma-delta
ASIC communications fault. Contact your Field Service Center.