EasyManua.ls Logo

Emerson ControlWave - Power Supply;Sequencer Module (PSSM)

Emerson ControlWave
156 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ControlWave Instruction Manual (CI-ControlWave)
Revised Nov-2010 Installation 2-7
Note: After you install the PSSM in the housing, as an added
precaution we recommend that you run a #14 AWG wire from
the TB2-5 power connection (chassis ground) to the same known
good earth ground.
Additional grounding guidelines include:
Use stranded copper wire (#4 AWG) for the housing to earth
ground, and keep the length as short as possible.
Clamp or braze the ground wire to the ground bed conductor
(typically a stranded copper AWG 0000 cable installed vertically or
horizontally).
Tin the wire ends with solder (using a high-wattage soldering iron)
prior to inserting the wire into the housing ground lug.
Run the ground wire so that any routing bend in the cable has a
minimum radius of 12-inches below ground and 8-inches above
ground.
2.3 Power Supply/Sequencer Module (PSSM)
Before we actually install the PSSM it in the housing, we’re going to
discuss some general information about how it works.

Table of Contents

Related product manuals