ControlWave Instruction Manual (CI-ControlWave)
Ranges &
Errors
Table 3-19 provides the accuracy, resolution and temperature range for
the various thermocouples and 10mV LLAI inputs. Table 3-20 lists the
RTD error with the CJC.
Table 3-19. LLAI Module Input Accuracy and Resolution
Input Type Accuracy/Range Resolution
25C –20C to +70C
B – Thermocouple
100C to 200C
200C to 390C
390C to 840C
840C to 1820C
2.00C
1.00C
0.50C
0.20C
8C
4C
2C
1C
16C
8C
4C
2C
R – Thermocouple
–50C to +50C
+50C to 1720C
0.40C
0.17C
2C
1C
4C
2C
S – Thermocouple
– 50C to +50C
+50C to 1760C
0.37C
0.18C
2C
1C
4C
2C
C – Thermocouple
0C to 2315C 0.16C 0.75C 1.5C
N – Thermocouple
– 270C to – 260C
– 260C to – 250C
– 250C to – 230C
– 230C to – 150C
– 150C to 1300C
1.50C
0.75C
0.50C
0.25C
0.09C
8C
4C
2C
1C
0.500C
10C
8C
4C
2C
1C
J – Thermocouple
– 210C to 191C
190C to 1200C
0.08C
0.11C
0.750C
0.500C
1.5C
1C
E – Thermocouple
– 270C to – 260C
– 260C to – 225C
– 225C to – 200C
– 200C to 1000C
1.00C
0.25C
0.08C
0.09C
3C
1C
0.750C
0.500C
6C
2C
1.5C
1C
K – Thermocouple
– 270C to – 261C
– 260C to – 246C
– 245C to – 180C
– 179C to – 145C
– 145C to 1372C
2.00C
0.56C
0.25C
0.08C
0.14C
5C
2C
1C
0.750C
0.500C
10C
4C
2C
1.5C
1C
T – Thermocouple
– 270C to – 261C
– 260C to – 251C
– 250C to – 181C
– 180C to – 136C
– 135C to – 400C
1.50C
0.38C
0.18C
0.08C
0.06C
4C
2C
1C
0.750C
0.500C
8C
4C
2C
1.5C
1C
10mV 10mV 1.2V 0.25% 0.05%
Note: The CJC RTD adds an additional error (see Table 3-20)
Table 3-20. LLAI Module RTD Error with CJC at 25
C
Thermocouple
Type
Process Temperature
Range
RTD Error with CJC
@ 25C
B
100C to 1820C 0.30C
R
– 50C to +50C
+50C to 1720C
0.49C
0.30C
S
– 50C to +50C
+50C to 1760C
0.45C
0.30C
Revised Nov-2010 I/O Modules 3-43