66 • iPro Case Controller I&O Manual FM V1.01 026-1738 Rev 1
EEPR_IntervU EEPR - Interval of updating-The time between updates for the output
position of the valve
0-60 Seconds
EEPR_MaxP EEPR - Max Opening Percentage 0-100%
EEPR_MinP EEPR - Min Opening Percentage 0-100%
EEPR_TimeInit EEPR - Time at Init Steps at the start time 1-200 Seconds
EEPR_del EEPR - Delay before EEPR is 0% caused by system disable 0-3600 Seconds
EEPR_ExtraS_Cal EEPR - Extra steps used for the first calibration after ExtraS_Cal_-
Time
1-2500 Steps
EEPR_LR EEPR - Min Regulation Alarm Threshold (rel) -40-90° relative to case temperature
setpoint
EEPR_MR EEPR - Max Regulation Alarm Threshold (rel) 0-90° relative to case temperature
setpoint
EEPR_HSHd EEPR - High Regulation Alarm Activation Delay 0-300 Seconds
EEPR_LSHd EEPR - Low Regulation Alarm Activation Delay 0-300 Seconds
EEPR_PB EEPR - Proportional Band (if 0, Regulation Auto Adaptive) of Regu-
lation
0-45°
EEPR_DB EEPR - Dead Band of Regulation -50-50°
EEPR_INC EEPR - Integral of Regulation 0-255 Seconds
EEPR_DER EEPR - Derivative of Regulation 0-255 Seconds
EEPR_ThrD EEPR - Threshold of Integral decrease (rel) -40-90°
EEPR_PercD EEPR - Percentage of integral decrease below the threshold 0-100%
EEPR_ExtraCl EEPR - Extra % of valve close in case of low alarm 0-500 Steps
EEPR_DutyCycle EEPR - Valve Duty Cycle 100%
EEV 1-3 Valve Parameters
EEV1_MinS EEV1 - Minimum Steps 0-50 where 1=10 Steps
EEV1_MaxS EEV1 - Maximum Steps 0-800 where 1=10 Steps
EEV1_PeakC EEV1 - Peak Current (Bipolar only) 0-100 where 1=10 mA
EEV1_HoldC EEV1 - Hold Current (Bipolar only) 0-100 where 1=10 mA
EEV1_StepR EEV1 - Step Rate 10-600 Steps
EEV1_ExtraS EEV1 - Extra Steps 1-500 Steps
EEV1_RelaxS EEV1 - Relax Steps 0-500 Steps
EEV1_PressF EEV1 - Filter on the pressure 1-100 Seconds
EEV1_TempF EEV1 - Filter on the temperature 1-100 Seconds
EEV1_InitS EEV1 - Steps Init Regulation Minimum of 2, maximum adjusts based
on MaxS. 1=10 Steps
EEV1_IntervU EEV1 - Interval of updating 0-60 Seconds
EEV1_MaxP
EEV1 - Max Opening Percentage 0-100%
EEV1_MinP EEV1 - Min Opening Percentage 0-100%
EEV1_TimeInit EEV1 - Time at Init Steps at the start time 1-200 Seconds
EEV1_del EEV1 - Delay before EEV1 is 0% caused by Enable DI 0-3600 Seconds
EEV1_ExtraS_Ca EEV1 - Extra steps used for the first calibration after ExtraS_Cal_-
Time
1-2500 Steps
EEV1_LSH EEV1 - Min Superheat Alarm Threshold 0-Setpoint
EEV1_MSH EEV1 - Max Superheat Alarm Threshold 0-90°
Table 16-1 - iPro Parameter List