Commissioning the Device in E2E iPro Parameter List • 67
EEV1_HSHd EEV1 - High Superheat Alarm Activation Delay 0-300 Seconds
EEV1_LSHd EEV1 - Low Superheat Alarm Activation Delay 0-300 Seconds
EEV1_PB EEV1 - Proportional Band (if 0, Regulation Auto Adaptive) of Super-
heat
0-45°
EEV1_DB EEV1 - Dead Band of Superheat -50-50°
EEV1_INC EEV1 - Integral of Superheat 0-255 Seconds
EEV1_DER EEV1 - Derivative Superheat 0-255 Seconds
EEV1_ThrD EEV1 - Threshold of Integral decrease -40-90°
EEV1_PercD EEV1 - Percentage of integral decrease below the threshold 0-100%
EEV1_ExtraCl EEV1 - Extra valve close in case of low superheating 0-500 Steps
EEV1_MOP EEV1 - Threshold of MOP -90-90°
EEV1_LOP EEV1 - Threshold of LOP -90-90°
EEV1_MOPLOPs EEV1 - Steps Close/Open in case of MOP/LOP 1-2500 Steps
EEV1_MOPLOPd EEV1 - Delay activation MOP/LOP 1-300 Seconds
EEV1_DutyCycle EEV1 - Valve Duty Cycle 0-100%
Lighting Control Parameters
LightOnHour Scheduled time for lights on (Hour) 0-23 Hours
LightOnMin Scheduled time for lights on (Minute) 0-59 Minutes
LightOffHour Scheduled time for lights off (Hour) 0-23 Hours
LightOffMin Scheduled time for lights off (Minute) 0-59 Minutes
Other Parameters
CF Temperature Measurement Unit °F or °C
PrU Pressure Measurement Unit PSI/BAR
Fty Gas Type R-22/R-407c/R-134a/R-404a/R-410a/
R-507/R-744 CO2/R-407a
StandaloneCC Y=Controller is standalone (no lineup); N=Controller is in a lineup Yes/No
S1Addr Configuration of slave device 1 address
0-247
S2Addr Configuration of slave device 2 address
S3Addr Configuration of slave device 3 address
S4Addr Configuration of slave device 4 address
S5Addr Configuration of slave device 5 address
Modbus_Addr Configuration of iPro itself
Baud Baud of ModBus communication 9600/19200
MSTPMac BACnet MS/TP MAC address 0-255
MSTPBaud BACnet MS/TP Baud rate 9600/19200
MSTPMaxMaster BACnet maximum master to poll for 0-127
MSTPAPDUTime BACnet APDU Timeout value 3-60 Seconds
ExtraS_Cal_Time Timer used for first calibration 0-480 Hours
RackID Rack ID See selection list
CircNum Circuit number 1-999
CaseID Case ID a-i
Refrigeration Control Parameters
LTSet
Low Temperature Setpoint -40-90°
Table 16-1 - iPro Parameter List