EasyManua.ls Logo

Emerson Network Power MPH2 - And Managed Receptacles (Type C, R and M Models); Branch Overcurrent Protection; Figure 1-5: Branch and Receptacle Identification-Units with Individually-Monitored

Emerson Network Power MPH2
51 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Introduction
Emerson
®
MPH2
User Manual 9
Figure 1-5 Branch and receptacle identification—Units with individually-monitored
and managed receptacles (Type C, R and M models)
1.3.4.1 Branch Overcurrent Protection
Models having more than 16-A input-current rating are equipped with branch overcurrent protection. The
branch circuit breaker is a UL 489-listed breaker with a flush-mount, rocker-style actuator. This protects
each receptacle group against overload and short circuit by interrupting the fault current flowing in the
line-to-line, line-to-neutral and line-to-PE conductors of the branch circuits. The branch circuit breaker
ratings apply over the full, rated operating temperature and frequency.
The flush-mount breakers guard against accidental trips that could interrupt power to the connected load.
Manually tripping a breaker requires a small, flat blade, such as a screw driver (see Figure 3-17).
Low-profile circuit breakers are used on all MPH2 Rack PDUs with two or three branch circuits less than
240-V rating in a line-neutral configuration. Standard-profile circuit breakers are used on MPH2 Rack
PDUs with six branch circuits or have a 240-VAC rating. Each type of circuit breaker is a rocker style (see
Figure 1-6).
The branch circuit breaker labeling (A, B, C and so on) shows which receptacles are protected by each
specific breaker. Receptacles on Branch A are protected by the circuit breaker labeled A. Three-phase
PDUs may also have labeling showing the phase associated with each circuit breaker.
Number Description
1 Branch identification
2 Receptacle identification
3
Receptacle-status LED (See 5.0 -
Troubleshooting, page 42.)
NOTE
The branch circuit breaker is not designed to be used as a disconnect device for the connected
load.

Table of Contents

Related product manuals