MPH2 Rack PDU Specifications
Emerson
®
MPH2
User Manual 41
4.0 Emerson
®
MPH2 Rack PDU Specifications
0-U 1-U 2-U
Input Power Configurations;
Vary by Model and Region
Single-Phase Input; CE-Mark
240 VAC, 16 A; also UL-listed 3.7 kW
230 V, 32 A 7.3 kW
Three-Phase Input; CE-Mark
230/400 V, 16 A 11 kW
230/400 V, 32 A 22 kW
Single-Phase Input; UL-Listed
120 VAC, 12 A 1.4 kW
120 VAC, 16 A 1.9 kW
120 VAC, 24 A 2.9 kW
208 VAC, 24 A 4.9 kW
Three-Phase Input; UL-Listed
120/208 VAC, 24 A 8.6 kW
120/208 VAC, 40 A 14.4 kW
120/208 VAC 48 A; 240/415 VAC, 24 A 17.3 kW
Input Wiring Options 10-ft. (3-m) Non-Detachable Power
Supply Cord
Hard-Wired Terminal Block
10-ft. (3-m) Non-Detachable Power Supply Cord
Receptacle Options NEMA 5-15; NEMA 5-20; IEC 320C13; IEC 320 C19
Number of Receptacles, Maximum 48 12 24
Power Consumption, Maximum 7.5 W
Measurement Accuracy
Voltage: ±1% +0.1 VAC
Current: ±1.5% + 0.01 A from 1% to 10% of unit rating;
±1% +0.01 A from >10% to 125% of unit rating
Insulation
Class I, Reinforced SELV
Dielectric Electric Strength
Tested up to 4242 VDC
Overcurrent Protection UL489-Listed, CSA, TUV, CCC Overcurrent Circuit Breaker,
20 A, 5000 A A.I.C
Operating Temperature Range, °F (°C) 32-A or Less Input Models: 32 to 140 (0 to 60)
40-A and 48-A Input Models without case ventilation: 32 to 122 (0 to 50)
40-A and 48-A Input Models with case ventilation: 32 to 140 (0 to 60)
Storage Temperature Range, °F (°C) -13 to 185 (-25 to 85)
Humidity,%
10 to 90 non-condensing
Altitude, ft. (m)
6562 (2000)
Mounting Factory-Installed Tool-less Brackets
Universal Mounting Bracket
Factory-installed, Right-angle Mounting Brackets
Width x Depth, in. (mm) Low-profile: 2.2 x 1.96
(56 x 50)
Standard: 2.2 x 2.7
(56 x 70)
1.73 x 9.84 (44 x 250) 3.46 x 9.84 (88 x 250)
Units, Length, in. (mm) 13.1 - 72.2 (333 - 1833) 19 (482.6) 19 (482.6)
Safety Standards
(Vary by Model and Region)
IEC 60950-1:2005 (Second Edition) + Amendment 1:2009
CSA C22.2 NO. 60950-1-07 (2nd Edition) + Amendment 1:2009
UL 60950-1 (2nd Edition) + Amendment 1:2009
IECEE CB Full Certification Scheme
EMC Standards
(Vary by Model and Region)
FCC Class A, Part 15, Industrial
EN55022:2006+A1:2007, Class A, Industrial
EN55024:1998+A1:2001+A2:2003, Class A, Industrial
IEC61000-3-2:2014 (ed.3), IEC61000-3-3:2013 (ed.3)
IEC61000-4-2/3/4/5/6/8/11
Note: A temporary loss of touch-key functionality may occur for sufficiently large radio-
frequency fields induced through the power-supply cord.
Agency Approvals
(Vary by Model and Region)
UL, cUL, CE, BV, CB, RoHS, REACH, WEEE