Installation
Emerson
®
MPH2
User Manual 15
2.3 Installing a MPH2 in an Emerson
®
Rack
2.3.1 Mounting Hardware and Tools Required
Factory-supplied
2 mounting brackets
2 mounting buttons
•4 spring nuts
Field-supplied
For mounting a vertical MPH2
Phillips #2 screwdriver
For mounting a horizontal MPH2:
Flat-blade screwdriver
Torx screwdriver TX30
Torque wrench
2.3.2 Mounting the Vertical MPH2
The vertical MPH2 can be installed on a vertical or horizontal frame member in the rack.
1. Determine where in the Emerson rack the PDU will be installed.
2. Attach a bracket to each end of the PDU.
3. If mounting on horizontal frame members, attach the brackets in-line, Figure 2-4.
- or -
If mounting on a vertical frame member, attach the brackets at a right angle to the PDU.
4. Insert two spring nuts into the appropriate T-slot on the frame member, Figure 2-4. Position the spring
nuts to accommodate screws inserted through slots in the brackets. To move the spring nuts, press
down on each with a small, pointed object and slide each into position.
5. Hold the PDU in place and attach the top of the unit to the rack with tool-less fasteners, Figure 2-4.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Network Power MPH2 and is the answer not in the manual?

Emerson Network Power MPH2 Specifications

General IconGeneral
BrandEmerson
ModelNetwork Power MPH2
CategoryPower distribution unit
LanguageEnglish

Related product manuals