Operation
30 Emerson
®
MPH2
™
User Manual
The default settings described in Table 3-1 apply only to MPH2, are set at time of manufacture and are
applied when “Restore to Factory Defaults” is initiated via RPC2 clients.
NOTE
For detailed information about settings and about network- and protocol-
related default settings for RPC2, see SL-20841. The document is available at
Emerson’s Web site: http://www.emersonnetworkpower.com
Table 3-1 Factory-default settings
Level Settings Default Value Units
Models
Affected Notes
PDU
User Assigned Label
MPH2 or
Rack PDU
<alpha>
—All
• RackPDU is default value the first time
only.
• Allowed characters include
alphanumeric, space,
and ~!#$_+`-={}|[]\\:;'?,.\/%^&*()@
Asset Tag 1 <empty> — All
Asset Tag 2 <empty> — All
Overcurrent Alarm Threshold 45 % All
• % calculated from maximum input-
current rating on nameplate.
• Default values are recommended for
dual-corded server applications.
Overcurrent Warning
Threshold
40 % All
Undercurrent Alarm Threshold 0 % All
Unbalanced Load Alarm
threshold
0%
All
3-phase
% difference calculated between any two
phases.
Software Over Current
Protection (SWOCP)
Disabled — R
Conditionally applies to unlocked and
unloaded receptacles only.
Branch
User Assigned Label Branch <alpha> — All
Allowed characters include
alphanumeric, space,
and ~!#$_+`-={}|[]\\:;'?,.\/%^&*()@
Asset Tag 1 <empty> — All
Asset Tag 2 <empty> — All
Overcurrent Alarm Threshold 95 % All
% calculated from CB rating. Refer to
nameplate for maximum branch current
rating.
Overcurrent Warning
Threshold
90 % All
Undercurrent Alarm Threshold 0 % All
SWOCP Disabled — R
Conditionally applies to all unlocked and
unloaded receptacles only for this
branch.