iTEMP TMT82 Technical data
Endress+Hauser 49
Standard Description Measuring range Measured error (±)
OIML R84: 2003, GOST
6651-94
Cu50 (14) –50 to +200 °C (–58 to +392 °F) ≤0.11 °C (0.2 °F)
0.1 °C (0.18 °F) + 0.004% x
(MV - LRV)
Resistance
transmitter
Resistance Ω 10 to 400 Ω
10 to 2 000 Ω
32 mΩ
300 mΩ
- 0.03 % (
4.8 µA)
1)
Measured value transmitted via HART
®
.
2) Percentages based on the configured span of the analog output signal.
3) Maximum measured error for the specified measuring range
Measured error for thermocouples (TC) and voltage transmitters
Standard Description Measuring range Measured error (±)
Digital
1)
D/A
2)
Maximum
3)
Based on measured value
IEC 60584-1
Type A (30) 0 to +2 500 °C (+32 to +4 532 °F) ≤1.31 °C (2.36 °F)
0.8 °C (1.44 °F) + 0.021% x
MV
0.03 % (
4.8 µA)
Type B (31)
+500 to +1 820 °C
(+932 to +3 308 °F)
≤1.43 °C (2.57 °F)
1.5 °C (2.7 °F) + 0.06% x
(MV - LRV)
IEC 60584-1 / ASTM
E988-96
Type C (32)
0 to +2 000 °C (+32 to +3 632 °F)
≤0.66 °C (1.19 °F)
0.55 °C (1.0 °F) + 0.0055% x
MV
ASTM E988-96 Type D (33) ≤0.74 °C (1.33 °F)
0.74 °C (1.33 °F) + 0.008% x
MV
IEC 60584-1
Type E (34)
–150 to +1 000 °C
(–238 to +1 832 °F)
≤0.22 °C (0.4 °F)
0.22 °C (0.4 °F) + 0.006% x
(MV - LRV)
Type J (35)
–150 to +1 200 °C
(–238 to +2 192 °F)
≤0.27 °C (0.49 °F)
0.27 °C (0.49 °F) + 0.005% x
(MV - LRV)
Type K (36) ≤0.35 °C (0.63 °F)
0.35 °C (0.63 °F) + 0.005% x
(MV - LRV)
Type N (37)
–150 to +1 300 °C
(–238 to +2 372 °F)
≤0.47 °C (0.85 °F)
0.48 °C (0.86 °F) + 0.014% x
(MV - LRV)
Type R (38)
+50 to +1 768 °C
(+122 to +3 214 °F)
≤1.11 °C (1.98 °F)
1.12 °C (2.0 °F) + 0.03% x
(MV - LRV)
Type S (39) ≤1.14 °C (2.05 °F)
1.15 °C (2.07 °F) + 0.022% x
(MV - LRV)
Type T (40) –150 to +400 °C (–238 to +752 °F) ≤0.35 °C (0.63 °F)
0.36 °C (0.65 °F) + 0.04% x
(MV - LRV)
DIN 43710
Type L (41)
–150 to +900 °C
(–238 to +1 652 °F)
≤0.29 °C (0.52 °F)
0.29 °C (0.52 °F) + 0.009% x
(MV - LRV)
Type U (42)
–150 to +600 °C
(–238 to +1 112 °F)
≤0.32 °C (0.58 °F)
0.33 °C (0.6 °F) + 0.028% x
(MV - LRV)
GOST R8.8585-2001 Type L (43)
–200 to +800 °C
(–328 to +1 472 °F)
≤2.16 °C (3.89 °F)
2.2 °C (3.96 °F) + 0.015% x
(MV - LRV)
Voltage transmitter
(mV)
–20 to +100 mV 10 μV 7.7 µV + 0.0025% x (MV -
LRV)
4.8 µA
1)
Measured value transmitted via HART
®
.
2) Percentages based on the configured span of the analog output signal.
3) Maximum measured error for the specified measuring range
MV = Measured Value
LRV = Lower Range Value of relevant sensor