Operating menu and parameter description iTEMP TMT82
68 Endress+Hauser
Prerequisite A thermocouple (TC) sensor must be selected as the sensor type.
Description Use this function to select reference junction measurement for temperature compensation
of thermocouples (TC).
If Preset value is selected, the compensation value is specified via the RJ preset
value parameter.
Temperature measured must be configured for channel 2 if Measured value
sensor 2 is selected
Options No compensation: no temperature compensation is used.
Internal measurement: the internal reference junction temperature is used.
Preset value: a fixed preset value is used.
Measured value sensor 2: the measured value of sensor 2 is used.
It is not possible to selected the Measured value sensor 2 option for the Reference
junction 2 parameter.
Factory setting Internal measurement
RJ preset value n
Navigation Setup → RJ preset value
Expert → Sensor → Sensor n →RJ preset value
Prerequisite The Preset value parameter must be set if the Reference junction n option is selected.
Description Use this function to define the fixed preset value for temperature compensation.
User entry –50 to +85 °C
Factory setting 0.00
Assign current output (PV)
Navigation Setup → Assign current output (PV)
Expert → Communication → HART output → Assign current output (PV)
Description Use this function to assign a measured variable to the primary HART
®
value (PV).