Operating menu and parameter description iTEMP TMT82
92 Endress+Hauser
Reset device temp. min/max values
Navigation Diagnostics → Measured values → Min/max values → Reset device temp. min/max
values
Expert → Diagnostics → Measured values → Min/max values → Reset device temp.
min/max values
Description Reset the peakhold indicators for the minimum and maximum electronic temperatures
measured.
Options No
Yes
Factory setting No
13.2.5 "Simulation" submenu
Simulation current output
Navigation Diagnostics → Simulation → Simulation current output
Expert → Diagnostics → Simulation → Simulation current output
Description Use this function to switch simulation of the current output on and off. The display
alternates between the measured value and a diagnostics message of the "function check"
category (C) while simulation is in progress.
Display Measured value display ↔ C491 (simulation current output)
Options Off
On
Factory setting Off
Additional information The simulation value is defined in the Value current output parameter.
Value current output
Navigation Diagnostics → Simulation → Value current output
Expert → Diagnostics → Simulation → Value current output
Additional information The Simulation current output parameter must be set to On.
Description Use this function to set a current value for the simulation. In this way, users can verify the
correct adjustment of the current output and the correct function of downstream switching
units.