Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus Operating menu
Endress+Hauser 165
A0013199
42 Distance for interface measurements
The unit is defined in the Distance unit parameter (→ 159).
Signal quality
Navigation Setup → Signal quality
Description Displays the signal quality of the evaluated echo.
Additional information Meaning of the display options
• Strong
The evaluated echo exceeds the threshold by at least 10 mV.
• Medium
The evaluated echo exceeds the threshold by at least 5 mV.
• Weak
The evaluated echo exceeds the threshold by less than 5 mV.
• No signal
The device does not find a usable echo.
The signal quality indicated in this parameter always refers to the currently evaluated
echo: either the level/interface echo
7)
or the end-of-probe echo. To differentiate between
these two, the quality of the end-of-probe echo is always displayed in brackets.
In case of a lost echo (Signal quality = No signal) the device generates the following
error message:
• F941, for Output echo lost (→ 199) = Alarm.
• S941, if another option has been selected in Output echo lost (→ 199).
7) Of these two echos the one with the lower quality is indicated.