Operating menu Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus
166 Endress+Hauser
Tank level
Navigation Setup → Tank level
Prerequisite Operating mode (→ 159) = Interface
Description Specify whether the tank or bypass is completely flooded or not.
Selection • Partially filled
• Fully flooded
Factory setting Partially filled
Additional information Meaning of the options
• Partially filled
The device searches for 2 echo signals, one for the interface and one for the total level.
• Fully flooded
The device searches for the interface level only. With this setting it is essential that the
upper level signal always is within the upper blocking distance (UB) in order to avoid
that it is evaluated by mistake.
A0013173
1 Partially filled
2 Fully flooded
UB Upper blocking distance
Distance to upper connection
Navigation Setup → Dist. up.connect
Prerequisite The device has the "Interface measurement" application package
8)
.
Description Specify distance D
U
to upper connection.
User entry 0 to 200 m
8) Product structure: Feature 540 "Application Package", Option EB "Interface measurement"