EasyManua.ls Logo

Endress+Hauser Liquistation CSF48 - Page 143

Endress+Hauser Liquistation CSF48
188 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Liquistation CSF48 Inputs: Oxygen
143
Diagnostic behavior
--> "Inputs: General/Frequently occurring functions" section ä 108
12.2.7 Tag control
--> "Inputs: General/Frequently occurring functions" section ä 108
12.2.8 Sensor replacement
--> "Inputs: General/Frequently occurring functions" section ä 108
12.2.9 Data processing factory setting
--> "Inputs: General/Frequently occurring functions" section ä 108
12.2.10 Sensor factory setting (only COS61D)
--> "Inputs: General/Frequently occurring functions" section ä 108
(Operation above second
specified nA value)
Only amperometric sensors, sensor-specific limit
COS22D: >50 nA
COS51D: >160 nA
Warning limit Factory setting
10000 h
Diagnostics code and associated message text:
185 "Operating time" (COS22D)
186 "Operating time" (COS51D)
Operation < 25 μs Only optical sensors (μS = fluorescence decay time, raw
value of optical measurement)
Warning limit Factory setting
10000 h
Diagnostics code and associated message text:
181 "Operating time"
Operation > 40 μs Only optical sensors
Warning limit Factory setting
10000 h
Diagnostics code and associated message text:
182 "Operating time"
Path: Menu/Setup/Inputs/DO/Extended setup/Diagnostics settings
Function Options Info