Liquistation CSF48 General settings
19
2.6.2 HART bus address
If Multidrop is active (Bus address > 0), the current at current output 1 is fixed at 4 mA.
Here, it does not matter what function has been assigned to the output (measured
value/controller etc.). Current simulation is no longer possible.
If you reset the device to the factory settings (Diagnostics/Systemtest/Reset/Factory
default), the bus address is not reset. Your setting is retained.
2.6.3 PROFIBUS DP
Detail information Read only Here you can find more information on the diagnostic
message and instructions on how to resolve the
problem.
Path: Menu/Setup/General settings/Extended setup/HART
Function Options Info
Bus address 0 to 63
Factory setting
0
You can change the device address to integrate several
HART devices in a network (Multidrop mode).
Path: Menu/Setup/General settings/Extended setup/PROFIBUS
Function Options Info
Enable Options
•Off
•On
Factory setting
Off
You can switch off PROFIBUS communication at this
point. The software can then only be accessed via local
operation.
Termination Read only If the device is the last in the bus, you can terminate via
the hardware.
--> BA00443C, "Wiring" section
Bus address 1 to 125 If you have addressed the bus via hardware (DIP swit-
ches on the module, --> BA00443C), you can only read
the address here.
If an invalid address is set via the hardware, you have to
assign a valid address for your device either here or via
the bus.
Path: ... /Extended setup/Diagnostics settings/Diag. behavior (optional)
Function Options Info