Operation Liquistation CSF48
160 Endress+Hauser
Outputting the status of a limit switch
Outputting diagnostics messages via the relay
You can output two categories of diagnostics messages via the relay:
1. Diagnostic messages from one of the 4 Namur classes
(--> see the "Adapting diagnostics information" section for more information on the Namur
classes)
2. Diagnostics messages which you have individually assigned to the relay output
A message is individually assigned to the relay output at 2 specific points in the menu:
Menu/Setup/General settings/Diagnostics/Device behavior
(device-specific messages)
Menu/Setup/Inputs/../Diagnostics settings/Diag. behavior
(sensor-specific messages)
Before being able to assign a special message to the relay output in "Device behavior", you
must first configure Outputs/relay x:y or /Alarm relay/Function="Diagnostics".
Function="LimitSwitch"
Function Options Info
Source of data Options
•None
Limit switch 1
Limit switch 2
Limit switch 3
Limit switch 4
Limit switch 5
Limit switch 6
Limit switch 7
Limit switch 8
Factory setting
None
Select the limit switch via which the status of the relay is
to be output.
The limit switches are configured in the
"Setup/Additional functions/Limit switches" menu.