32
Initial Installation
QUALIFIED INSTALLERS ONLY
minimum toP vent configuRations
3” (7.6 cm)
Minimum Rear
Clearance
Exterior Wall
B
Minimum
Horizontal Length
A
Minimum
Vertical Length
Approved through
wall thimble
Minimum Height
Pole Pedestal:
62.5” (158.8 cm)
Wood Pedestal:
63.25” (160.7 cm)
Termination Style
[Refer to table]
Figure 49: Minimum Vent Conguration - Top Vent
Refer to Table 6 and Figure 49 below for the minimum allowable top venting setup for the S50.
*Note: When installing above minimum allowable venting any horizontal termination listed in Table 4 on page
29 is permitted for use.
A” [Vertical Rise] B” [Horizontal Run] Termination Type
NG
12” [Min.]
12” Max Out Straight Termination
48” Max Out 36” Snorkel
18 18” Max Out Straight Termination
24” 48” Max Out Straight Termination
LP 24” [Min.]
18” Max Out Straight Termination
24” Max Out 14” Snorkel
48” Max Out 36” Snorkel
Table 6: Minimum Top Vent Congurations