Enviro S50 - Rear Vent and Horizontal;Vertical Termination; Minimum Rear Vent Configurations

Enviro S50
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
Initial Installation
QUALIFIED INSTALLERS ONLY
3” (7.6 cm)
Minimum Rear
Clearance
Exterior Wall
Approved through
wall thimble
Tremination Style
[Refer to table]
A
Minimum
Horizontal Length
Minimum Height
Pole Pedestal:
40” (101.6 cm)
Wood Pedestal:
40.75” (103.5 cm)
Figure 52: Minimum Vent Conguration - Rear Vent
minimum ReaR vent configuRations
Refer to Table 7 and Figure 52 below for the minimum allowable rear venting setup for the S50.
*Note: ALL rear vent configurations require a snorkel style termination.
A” [Horizontal Run] Termination Type
NG
18” [Max] 14” Snorkel
up to 36 36” Snorkel
LP 9” [Min.] - 18” [Max] 36” Snorkel
Table 7: Minimum Rear Vent Congurations
*Note: When performing an LP Rear Vent Corner Install with 4Elbow, a DURAVENT 36SNOR-
KEL MUST BE USED. The 45° elbow accounts for 6” of vent run.