EasyManua.ls Logo

Erbe ICC 300 H-E - Adjustment 5 - HF Generator Output Parameters

Erbe ICC 300 H-E
266 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1 TEST PROGRAMS AND ADJUSTMENTS70 / 266
Adjustment 5
HF generator output parameters
Procedure
Call up Test program 16, Adjustment 5.
Connect the HF power meter, e.g. APM 600 (set to 500 ohms) via active cable to active and neutral
electrode output sockets on the ICC; for 2 monopolar outputs: CUT / COAG 2 output and NE socket.
Activate the unit with the yellow pedal of the footswitch (AUTO CUT).
Using TP3 on the control board (slot J3), the HF output voltage is set in such a way that a power of
100 watts is indicated on the HF power meter and a value of 223 volts HF effective voltage (tolerance
220…223 volts) in the display on the AUTO CUT field.
Under certain conditions, TP 4 (HF current limitation) must be turned back far enough before this
setting so that no current limitation is effective.
Using TP4 on the control board (slot J3), the HF current limitation is set in such a way that a value of
447 mA effective HF current (tolerance 439…447 mA) with constant power output appears in the
AUTO COAG 1 field.
Insofar as the measurement of the phase angle between HF voltage and HF current produces a value
greater than 98 (which is 100 · cos j) at this setting in the AUTO COAG 2 field, a value of 100 watts
HF power output is displayed (tolerance 97...100 watts) in the AUTO BIPOLAR field after correct
adjustment of voltage and current.
For the voltage characteristic at a 500 ohms load, see Fig.
ICC 350
ICC 300
AUTO CUT AUTO COAG 1 AUTO COAG 2 AUTO BIPOLAR
Ab 5 UI before activation
U HF I HF cos Phi P during activation
ICC 200
AUTO CUT AUTO COAG
UI before activation
U HF I HF after activation
• U HF HF voltage [V]; Set value = 223 V
• I HF Real part of HF current [mA]; Set value = 447 mA

Table of Contents