8.4 Power Supply
The equipment shall be supplied by a double-reinforced SELV source. A circuit
breaker with a rating of maximum 16 A shall be incorporated into the circuit.
8.4.1 MINI-LINK E
Power Supply
Input DC Voltage 24 60 V DC, nominal
(20.4 72.0 V DC including
tolerance)
Power Consum ption for MINI-LINK E with RAU1
Table 33 Maximum terminal power consumption for MINI-LINK E w ith RAU1
Traffic capacity [Mbit/s]
Terminal type
2x2 4x2 8x2 17x2
Unprotected 42 W 44 W 49 W 54 W
Protected
88 W 92 W 94 W 101 W
With SAU, ETU, fan unit and MXU add 10 W each.
Power Dissipation for MINI-LINK E with RAU1
Table 34 Maximum terminal power dissipation for MINI-LINK E with RAU1
Traffic capacity [Mbit/s]
Terminal type
2x2 4x2 8x2 17x2
Unprotected
12 W 14 W 19 W 24 W
Protected
28 W 32 W 34 W 41 W
With SAU, ETU, fan unit and MXU add 10 W each.