8.9 Fan Unit Data
The fan unit contains four fans for increase of the airflow through the plug-in
units in the AMM.
If the indoor location has forced cooling through the m agazine with an airflow of
at least 10 m
3
/h (3.3 g/s or 170 l/min) no other cooling arrangement is required.
Power Supply
Power supply 24 60 V, nominal
(20.4 72.0 V including tolerance)
Maximum power consumption 10 W
8.10 DDU Data
Power Supply and Output Current
Power supply 24 60 V, nominal
(20.4 72.0 V including tolerance)
Maximum output current 6 A per connector
8.11 PSU Data
Cables
Connection to AC mains supply can be done by using the AC cable (ETSI) RPM
945 04 or any locally approved standard cable with an IEC 320-C14 inlet.
Interfaces
AC input Inlet in accordance with IE C 320-C14
Fuses Two T 3.15 AH 250 V
ON/OFF switch
DC output Numbers: 3
2-pin D-sub connector with fem ale insert
Ground In accordance with EN 60 950