2.5.3 Output for alarm siren fault
The fault output connector terminals are identified and marked as FAULT.
The output is normally supervised, but it is possible to change the type of set-up by acting on the software
configuration (see chapter 9.2.4) e hardware (by the Jumpers SEL1”). In the case of selection of output
supervised, an end of line resistor of 5.6K - 1/4Watt needs to connect on the last siren of the line.
For the maximum power allowed on every output, see pg. 90 of this chapter.
It is advisable to always use a fire-resistant, double twisted and protected cable for the installation.
Depending on how the “CONFIG.” parameters are set-up (see chapter 9.2.4), it is necessary to modify, while the
control Panel is off, and the relative Jumpers to “SEL1”:
SUPERVISED OUTPUT
SIREN
5.6 Kohm, 1/4W
5.6 Kohm, 1/4W
-
2
4
+
2
4
S
H
I
+
S
-
S
- +
FAULT
S
H
I
OC 1
O
C
2
O
C
3
O
C
4
RL2
RL1
SEL4
SEL3
SEL1
SEL2
Only in this case the output is protected by a fuse (see chapter 2.5).
OUTPUT 24V MISSING
SELF-POWERED
SIREN
5.6 Kohm, 1/4W
-
2
4
+
2
4
S
H
I
+
S
-
S
- +
FAULT
S
H
I
OC 1
O
C
2
O
C
3
O
C
4
RL2
RL1
SEL4
SEL3
SEL1
SEL2
COMMAND: POSITIVE DISCONNECTED
+
-
OUTPUT RELAY NOT SUPERVISED N/O
SIREN
5.6 Kohm, 1/4W
-
2
4
+
2
4
S
H
I
+
S
-
S
- +
FAULT
S
H
I
OC 1
O
C
2
O
C
3
O
C
4
RL2
RL1
SEL4
SEL3
SEL1
SEL2
+
-

Table of Contents

Related product manuals