EasyManua.ls Logo

FDP EX-CPL - 15.2 RESETTABLE BUTTON

FDP EX-CPL
91 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 73 of 91
Rev. 4.
2
0
15.1.6 Electrical schemes
2
2
3
3
1
1
6
6
5
5
4
4
SH I
Lo op +
Lo op -
SH I
Lo op +
Lo op -
CONNECTION TO LOOP:
OUTSIDE DOORREPEATER:
-
+
15.2RESETTABLE BUTTON
Manual reset alarm button for control panel.
15.2.1 Input and output description
INPUT: The input is of the type of balanced resistance of the 27K value. The input signal is given opening the
circuit between the two clips and the resistance; but, if it is short circuited, a fault in the input line is indicated. The
maximum length of the input line is 8m.
OUTPUT: the output is a Open Collector type. It is necessary to use a CMOS interface with a low current supply
to control a relay.
The input and output can be programmed with different types of meaning (Example: Alarm fire, technological...).
15.2.2 Button addressing
For the addressing in loop it is necessary to use a magnet near the reed. For the procedures, refer to the manual
of the control panel.
15.2.3 Manual zero setting of the address
Normally the factory address is equal to 0 (zero). If you must assign the address to zero, give manually 24V to the
detector and, after ten seconds, approach reed a magnet and wait for the led to make a long flash signal.
15.2.4 Point setting
In the “Point setting” menu (submenu of “POINT” item) there are different parameters for this detector. For
the output setting, see chapter PART 9).

Table of Contents

Related product manuals