Festo Controller CECC
68
Error message Error
no.
Error
class
Remedy
IoDrv: Overload 2 Warning Check the outputs for possible short circuit.
IoDrv: IO power supply
failure
4 Warning Check the I/O power supply.
Undervoltage in power
supply
5 Warning Check the power supply.
Error loading bootproject 120 Warning Check your boot project.
FPGA open failed 140 Error Replace the device.
FRAM open failed 141 Error
Runtime license invalid 144 Error
Codesys started 210 Information –
Codesys shutdown 211 Information –
Change to run state 212 Information –
Change to stop state 213 Information –
Wait for USB device
connection
220 Information Deactivate the function for transferring project data
using a USB memory stick.
Table: Codesys error messages
Error message Error no. Error class Remedy
IOLinkDrv: Initialization
failed
150 Error Check the connected IO-Link devices.
Check the power supply.
IOLinkDrv: Stack halted
(Error)
151 Error
IOLinkDeviceDrv:
Initialization failed
152 Error
IOLinkDrv: Started 214 Information –
IOLinkDeviceDrv: Started
215 Information –
Table: IO-Link error messages
Error message Error no. Error class Comment
multicast daemon started 216 Information –
Kernel diagnosis daemon
stopped
217 Information –
Kernel diagnosis daemon
started
218 Information –
Redirect all kernel errors to
diagnostics
219 Information –
Table: Internal error messages