EasyManua.ls Logo

FireFlex TOTALPAC2 - Page 60

FireFlex TOTALPAC2
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 10 of 12 TOTALPAC2
TOTALPAC2 Integrated Fire Protection System
Deluge System - Programming & Field Wiring Diagram
FM-086G-0-38E
ZONE 1
-
+
-
+
-+ -+
+-
ZONE 2
Wiring in Class A (style D)
Included CA2Z will
convert Zone 1 & Zone 2
Class-B Zones into two
Class-A Zones
Note: ELR, are not
required on Class-A
Program #5 / Factory pre-wired Zones:
SUP.1=Valve Tamper
SUP.2=Low Air (n/a on Deluge)
ZONE 2=Low Air Alarm (n/a on Deluge)
ZONE 3=Waterflow
OUT 3=Releasing Solenoid
Input Wiring in Class B (style B)
+
-
+
-
+
-
SUP.2SUP.1
AUX.
POWER
24VR DC
TB101
TB103
COM
NO
COM
NO
COM
NO
NC
COM
NO
NC
TROUBLE
ALARM
SUPV
WATER
FLOW
Auxiliary dry contact relay outputs
rated 3A at 30Vdc (resistive)
+
-
ZONE 1
+
-
ZONE 2
+
-
ZONE 3
+
-
ZONE 4
TB102
Output Wiring in Class B (style Y)
S+
-
+
-
RS-485 24VDC
non reset.
4
5
3
2
0
1
6
7
8
9
TB1
AC POWER SUPPLY
120 VAC, 60Hz / 220VAC, 50Hz
CIRCUIT IS NON-POWER LIMITED
AND SUPERVISED
LG
N
An individual branch circuit shall be required
for the supply of the control panel power source
!
END OF LINE DEVICE
EOL
DRY CONTACT DEVICE
MANUAL PULL STATION
SMOKE DETECTOR
NOTIFICATION BELL
HEAT DETECTOR
M
Legend
NEUTRAL
GROUND
LINE
AIR COMPRESSOR
1 HP Maximum
120Vac, 60Hz 220Vac, 50 Hz
Wiring size: Minimum 14 AWG with 600V Insulation.
Wiring of 120/220Vac Air Compressor
Power Source
INPUT POWER SOURCE
FM-086V-0-25B
Branch circuit for air compressor shall not be the same
as the control panel power source
!
EOL
+
-
+
-
+
-
EOL
+
-
EOL
5.1K, 1/4W
ELR (Typical)
+
-
EOL
+
-
EOL
FIELD WIRING DIAGRAMS
EOL
+
-
+
-
M
M
4
2
1
TBB
3
-
+
OUT 1 OUT 2 OUT 3 OUT 4
EOL
5.1K, 1/4W
ELR (Typical)
EOL EOL
-
+
-
+
-
+
S
EOL DIODE
ASSY
NYC
Power Limited (supervised) Initiating Device Circuits
Detection Zone 1, 2, 3, and 4.
Max. loop resistance: 100 ohms
End of line: 5.1K ohms, 1/4W
Leave ELR (provided) on all unused circuits.
Refer to Device Compatibility in the VFR-400 Control Panel
Manual.
Power Limited (supervised) Initiating Device Circuits
Supervision Zone 1, and 2.
Max. loop resistance: 100 ohms
End of line: 5.1K ohms, 1/4W
Leave ELR (provided) on all unused circuits.
For dry contact supervisory devices such as tamper, low air, or
high air switches. (Class-B only)
Power Limited (supervised) Notification Appliance Circuits
Output Circuit 1, 2, 3, and 4
Maximum operating voltage: 27Vdc (ripple: 0.3Vdc)
Maximum usable current per circuit: 1.0A
Total current available (all circuits): 2.5A
Polarity is reversed in supervisory condition.
Leave ELR (provided) on all unused circuits.
Refer to Device Compatibility in the VFR-400 Control Panel
Manual.
Auxiliary Power 24Vdc Regulated Source
Total current available: 0.2A
Resettable for 4 wires smoke detectors

Table of Contents

Other manuals for FireFlex TOTALPAC2