2 Integrated Fire Protection System
General Section - Deluge System
FM-086G-0-15E
4. General Description
There are several types of deluge systems, but all of
them use open type sprinklers and / or spray nozzles in
the sprinkler piping which totally flood an area with
pressurized water. A detection network is used in parallel
with the open type sprinkler / nozzles system. This
network may be hydraulic, pneumatic or electric and may
be actuated by manual, fixed temperature, rate-of-rise
temperature, smoke or other means. When the detection
system operates it gives an alarm and activates the
deluge valve. Because deluge systems are often used in
extra-hazard occupancies, electrical and pneumatic
detection systems are by far the most common.
The T
OTAL
P
AC
2 integrated fire protection system by
FireFlex Systems Inc. consists of a deluge system trim
totally pre-assembled, pre-wired and factory tested. All
electrical and mechanical components of the system are
contained in one single unit.
Note: Skid units include the trim components only and
must be wired by the installing contractor.
The only connections required for installation are the
water supply inlet, water discharge outlet, main drain, and
the electrical detection and alarm connections. The
discharge outlet is connected to a fixed piping system of
open sprinklers and or nozzles. Water is the
extinguishing agent.
Deluge systems are usually supervised. The T
OTAL
P
AC
2
system is supervised in order to monitor its integrity. The
electrical detectors and associated wiring are also
supervised.
The most common applications are protection of extra-
hazard occupancies by creating a fire buffer zone or by
cooling surfaces to prevent deformation or structural
collapse. Examples: storage or process areas containing
substances having a low flash point; areas in which fire
may spread rapidly; tanks containing combustible
solutions, transformers, equipment pits or product
handling systems.
Systems should be designed by qualified fire-protection
engineers in conjunction with the appropriate Authority
Having Jurisdiction.
Note: Each T
OTAL
P
AC
2 Unit is identified with it's unique
Serial Number. This number is located on a sticker
inside the main door panel and is used to maintain a
record in our computerized data base. Have this Serial
Number handy when calling for information on your unit
(format is TOT##### or TOTS#### for skids).
5. Features
Your T
OTAL
P
AC
2 unit is superior than many other products
available on the market now and has been manufactured by
the company that has introduced and developed the concept
of integrated fire protection systems in the market.
Main features are:
- Trouble free design for safe and easy application
- Available in 5 sizes from 1½" to 6" diameter
- Uses the Viking Deluge Valve
- Available and Listed both with or without Integrated Control
Panel
- Compact, aesthetic and easy to move
- User-friendly standardized owner's manual with every unit
- Unique serial number on every unit
- Uses only UL, C-UL Listed and FM Approved components
- Designed in accordance with NFPA Standards
- Trim is fully assembled and tested at the factory
- Water supply and drain connections on both sides,
available both with grooved end or flanged fittings
- Sturdy 14 Gauge steel cabinet or skid painted fire red with
oven baked polyester powder on phosphate base
- Textured rust proof finish
- Neoprene gasket on all doors to eliminate vibrations
- Easily removable doors for ease of access
- Key-alike locks on all cabinet doors
- Manufactured under ISO-9001 quality control procedures.