–49–
✱
33 ALARM BELL TIMEOUT ÊÊ1ÊÊ
0 = No timeout
1 = 4 min
2 = 8 min
3 = 12 min
4 = 16 min
This field determines whether the external sounder will shut off after
time allotted, or continue until manually turned off.
UL installations: must be set for a minimum of 4 min (option 1)
✱
34 EXIT DELAY Ê7Ê|Ê0Ê Ê7Ê|Ê0Ê
00-99 = exit delay time for each partition in seconds
The system will wait the time entered before sounding an alarm if the
exit door is left opened after the system has been armed.
✱
35 ENTRY DELAY 01 ÊÊ ÊÊ3|Ê0Ê ÊÊÊÊÊÊÊÊ ÊÊ3|Ê0Ê
00-99 = entry delay time for each partition in secs. Part. 1 Part. 2
The system will wait the time entered before sounding alarm upon
entering.
UL installations: must be set for a maximum of 20 seconds
✱
36 ENTRY DELAY 02 ÊÊ ÊÊ6|Ê0Ê ÊÊÊÊÊÊÊÊ ÊÊ6|Ê0Ê
00-99 = entry delay time for each partition in secs. Part. 1 Part. 2
The system will wait the time entered before sounding alarm upon
entering.
UL installations: must be set for a maximum of 20 seconds
✱
37 AUDIBLE EXIT WARNING ÊÊ ÊÊ1ÊÊ ÊÊÊÊÊÊÊÊ ÊÊ1ÊÊ
0 = no exit warning sound Part. 1 Part. 2
1 = provide exit warning sound when armed AWAY
Warning sound consists of slow continuous beeps until last 5 seconds,
when it changes to fast beeps. The warning sound will end at the
termination of Exit time.
✱
38 CONFIRMATION OF ARMING DING ÊÊ ÊÊ0ÊÊ ÊÊ ÊÊÊ ÊÊ0ÊÊ
0 = no ding Part. 1 Part. 2
1 = confirmation ding after arming system
2 = confirmation ding after arming from RF button or RF keypad only
(ding occurs when the system receives the RF transmission.)
Confirmation of arming is 1/2 second external sounder ÒdingÓ when
closing report is sent, or at the end of exit delay.
✱
39 POWER UP IN PREVIOUS STATE ÊÊÊ1Ê
0 = always power up in a disarmed state
1 = assume the system status prior to power down
When the system powers up armed, an alarm will occur 1 minute after
arming if a zone is faulted.
Note that if the previous state was armed AWAY or STAY, the system
will not respond to sensor changes for 1 minute, which allows time for
sensors such as PIRs to stabilize.
UL installations: must be 1 (power up in previous state)