FLUXUS WW 16 Outputs
114 UMFLUXUS_WWV1-1EN, 2018-02-28
16.1.3 Function test
Connect a multimeter to the installed output.
Test of the analog outputs
Test of the binary outputs
16.2 Error value delay
The error value delay is the time interval after which the entered error value is transmitted to the output in case no valid
measured values are available. The error value delay can be entered in the program branch Output Options if this
menu item has previously been activated in the program branch Special Funct.. If the error value delay is not entered,
the damping factor will be used.
The current output is tested. Enter a test value. It has to be within the output range. Press
ENTER.
If the multimeter displays the entered value, the output functions correctly.
Select yes to repeat the test, no to return to SYSTEM settings. Press ENTER.
Select Opto-Relay OFF in the scroll list Output Test to test the de-energized state of
the output. Press ENTER. Measure the resistance at the output. The value has to be high
ohmic.
Select yes. Press ENTER.
Select Opto-Relay ON in the scroll list Output Test to test the energized state of the
output. Press ENTER. Measure the resistance at the output. The value has to be low ohm-
ic.
Select yes to repeat the test, no to return to SYSTEM settings. Press ENTER.
Select Special Funct.\SYSTEM settings\Dialogs/Menus\Error-val. delay.
Select damping if the damping factor is to be used as the error value delay. Select edit to
activate the menu item Error-val. delay in the program branch Output Options.
From now on, the error value delay can be entered in the program branch Output Op-
tions.
I1= 4.0 mA
Again? no >YES<
B1:Output Test ↕
Opto-Relay OFF
B1:Output Test ↕
Opto-Relay ON
Error-val. delay
>DAMPING< edit