EasyManua.ls Logo

Fluke 1672 - Zmax; Auto Start; Loop Impedance Test with 10 Ma RCD

Fluke 1672
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Multifunction Tester
Applications
55
Zmax
Zmax compares multiple line/loop impedances and retains the maximum impedance. Sockets
on a circuit can be tested consecutively and the maximum impedance value retained and
stored to memory.
Zmax has a toggle on/off switch. There are two types of Zmax values: Zmax (L-PE) and Z
I
Zmax
(L-N). The input selection determines which Zmax value is in use:
Z
I
No Trip
L-N: Z
I
Zmax is in use
L-PE: both Z
I
Zmax and Zmax are in use
Z
I
Trip (Hi Current)
L-N: Z
I
Zmax is in use
L-PE: Zmax is in use
The Zmax values are retained when you switch between Z
L
No Trip and Z
L
Hi Current. Zmax
values are saved with the test result to memory.
Auto Start
Auto Start enables faster testing. When the Tester detects mains voltage in the loop/line or
RCD tests, the test starts automatically without pushing
T.
Loop Impedance Test with 10 mA RCD
For a Loop impedance measurement in a 10 mA RCD circuit, Fluke recommends the tripping
time RCD test. Use a nominal test current of 10 mA and the factor x ½ for this test.
If the fault voltage is <25 V or 50 V, dependent on the local requirement, the loop is good. To
calculate the loop impedance, divide the fault voltage by 10 mA (Loop impedance = fault
voltage x 100).

Table of Contents