EasyManua.ls Logo

Frick Vyper 700 - Programming PID Setup

Frick Vyper 700
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VYPER
VARIABLE SPEED DRIVE
OPERATION
100-210 IOM (JUL 09)
Page 41
PROGRAMMING PID SETUP
Step 1: (See Figure 40) The PID Setup Screen requires
programming so that the Quantum
LX panel will control
the cooling system for the Vyper
Drive. Advance to the
PID Setpoints Screen by pressing the [MENU] key and then
selecting Setpoints”, PID Setup”, and Page 2 .
Step 2: (See Figure 40) Use the cursor arrow and [Tab] keys
to navigate between setpoints. With the keypad, program the
parameters listed in Table 13 under “PID #5 on the PID Setup
Screen. Press the [Enter] key to accept each setpoint.
Step 3: Press the [Submit] key to accept the changes to PID
Channel 5 and return to the operating status screen.
Figure 40 - PID Setup Screen (Page 2)
PID Parameter Value
Name Drive Cooling
Control Running
Action Forward
Control Point Vyper
Coolant*
Device Source Analog Board 2
Device Channel 1
Setpoint 100°F
Dead Band 0.0°F
Proportional Band 20°F
Integration Time 30
High Limit 100%
Low Limit 0%
When Running OFF Value 0%
Table 13 – PID Channel #5 Setpoints

Table of Contents

Related product manuals