VYPER
™
VARIABLE SPEED DRIVE
OPERATION
100-210 IOM (JUL 09)
Page 41
PROGRAMMING PID SETUP
Step 1: (See Figure 40) The PID Setup Screen requires
programming so that the Quantum
™
LX panel will control
the cooling system for the Vyper
™
Drive. Advance to the
PID Setpoints Screen by pressing the [MENU] key and then
selecting “Setpoints”, “PID Setup”, and “Page 2” .
Step 2: (See Figure 40) Use the cursor arrow and [Tab] keys
to navigate between setpoints. With the keypad, program the
parameters listed in Table 13 under “PID #5” on the PID Setup
Screen. Press the [Enter] key to accept each setpoint.
Step 3: Press the [Submit] key to accept the changes to PID
Channel 5 and return to the operating status screen.
Figure 40 - PID Setup Screen (Page 2)
PID Parameter Value
Name Drive Cooling
Control Running
Action Forward
Control Point Vyper
™
Coolant*
Device Source Analog Board 2
Device Channel 1
Setpoint 100°F
Dead Band 0.0°F
Proportional Band 20°F
Integration Time 30
High Limit 100%
Low Limit 0%
When Running OFF Value 0%
Table 13 – PID Channel #5 Setpoints