EasyManua.ls Logo

Frick Vyper 700 - Compressor Safeties Screen

Frick Vyper 700
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VYPER
VARIABLE SPEED DRIVE
OPERATION
100-210 IOM (JUL 09)
Page 51
Compressor Safeties Screen
To prevent the Slide Valve from unloading beyond a high
setpoint level (97%) and permit rapid compressor response
under load, make the following setting adjustments on the
Compressor Safeties Screen:
Step 1: Press the [MENU] key and then selecting Setpoints
and Compressor”. Press the [ENTER] key to advance to the
Compressor Safeties Screen.
Step 2: (Refer to Figure 61) Use the cursor arrow and [Tab]
keys to navigate to the “Highest Capacity To Permit Start-
ing” (Callout 1) and “Compressor Automatic Mode Minimum
Capacity” (Callout 2). Use the keypad to program the set-
points to 97%”. Press the [Enter] key to accept the value
for each field.
Step 3: Press the [Submit] key to accept the changes and
return to the operating status screen.
Figure 61 - Compressor Safeties Screen
1
2

Table of Contents

Related product manuals