EasyManuals Logo

Froling P4 User Manual

Froling P4
51 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #35 background imageLoading...
Page #35 background image
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 35
Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com B0430207
4
4.7.2 Temperature Settings for the Solar System
Setting value
Description
DHW tank temperature setpoint
during solar charging 75°C
Up to this temperature the DHW tank is heated by the solar
system.
Temp differential to start
collector pump 10°C
The collector loading pump activates when the collector
temperature exceeds the storage or DHW tank temperature by this
value.
Temp difference to stop
collector pump 5°C
The collector loading pump activates when the collector
temperature exceeds the storage or DHW tank temperature by this
value.
Maximum storage tank
bottom temperature during
solar charging 85°C
Maximum bottom storage tank temperature at which the collector
pump is switched off (only with storage tank).
4.8 Menu-Pellets
4.8.1 Fuel Filling Times
Setting value
Description
Start of 1
st
pellet filling 9:00
1
st
Start time for filling. This is only carried out if the fill level in
the container is under 85%.
Start of 2
nd
pellet filling 15:00
2
nd
Start time for filling. This is also only carried out if the fill level
in the container is under 85%.

Table of Contents

Other manuals for Froling P4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Froling P4 and is the answer not in the manual?

Froling P4 Specifications

General IconGeneral
ModelP4
CategoryBoiler
Fuel TypeWood Pellets
Automatic IgnitionYes
Automatic CleaningYes
Touchscreen ControlYes
Remote MonitoringYes
WeightVaries depending on model
Dimensions (H x W x D)Varies depending on model

Related product manuals