Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 35
Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com B0430207
4
4.7.2 Temperature Settings for the Solar System
Setting value
Description
DHW tank temperature setpoint
during solar charging 75°C
Up to this temperature the DHW tank is heated by the solar
system.
Temp differential to start
collector pump 10°C
The collector loading pump activates when the collector
temperature exceeds the storage or DHW tank temperature by this
value.
Temp difference to stop
collector pump 5°C
The collector loading pump activates when the collector
temperature exceeds the storage or DHW tank temperature by this
value.
Maximum storage tank
bottom temperature during
solar charging 85°C
Maximum bottom storage tank temperature at which the collector
pump is switched off (only with storage tank).
4.8 Menu-Pellets
4.8.1 Fuel Filling Times
Setting value
Description
Start of 1
st
pellet filling 9:00
1
st
Start time for filling. This is only carried out if the fill level in
the container is under 85%.
Start of 2
nd
pellet filling 15:00
2
nd
Start time for filling. This is also only carried out if the fill level
in the container is under 85%.