4.9 Menu-Boiler
4.9.1 Status Displays for the Boiler
Actual state values of boiler control system
:
:
Flue gas temperature 176°C
Boiler control variable 95%
Air Speed at suction 0.00 m
opening
Ignition pipe temperature 0°C
Calculated boiler set-point 70°C
4.9.2 Temperature Settings for the Boiler
Boiler temperature set-point 80°C
The boiler temperature is regulated to this value. (Range: 40-
70ºC) Recommendation: System without storage tank 50ºC,
System with storage tank 70ºC.
Shutdown if current boiler
temperature is higher than boiler
temperature set-point + 15ºC
If the boiler temperature exceeds the set-point by this parameter
value, the boiler switches to constant burn status. The boiler
starts up again below the temperature set-point.
Always switch off above highest
possible boiler temperature set-
point + 3ºC
If the boiler temperature exceeds the maximum set-point by this
parameter, the boiler switches to constant burn status. The
heating circuit and store loading pumps will also begin to run to
cool the boiler. The boiler starts up again below the temperature
set-point.
Minimum boiler temperature to
release all pumps 35ºC
The pumps are released at this boiler temperature. (Hysteresis
2ºC).