EasyManua.ls Logo

Fronius CL - PE Conductor Resistance Testing

Fronius CL
138 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
126
Electrical Tests
PE Conductor Re-
sistance
The PE conductor resistance test is to be carried out with the cabinet doors open.
- Ensure that the device to be tested is safely disconnected from the AC mains. The grid
leads (L1, L2, L3, N) must not be connected. Observe safety rules.
- Ensure that the device to be tested is safely disconnected from the DC mains. DC ca-
bles must not be connected. There may be a DC voltage in the cables. Follow safety
rules.
- During the measurement, all switches, controls, etc., must be closed.
- AC protection and DC main switch must be activated.
- The module grounding (if present) must be removed from the inverter during the in-
spection.
- Disconnection is required from SolarNet and Datcom Ring.
1 Measuring instrument
2 Inverters
9 Measuring leads
Example: Measurement of the ground conductor re-
sistance
(1) Ground terminal
(2) Example measurement point.
- Measurements are taken between the ground terminal (1) of the device and each
touchable, conductive part connected with the ground conductor (e.g. 2).
- The resistance must not exceed 0.3 Ω *)
*) These requirements relate to DIN VDE 0701-0702 and ÖVE/ÖNORM E8701-1. In addi-
tion, individual national requirements and standards must also be observed.
(1)(2)

Table of Contents

Related product manuals