Fronius CL - Service Class 5: Non-Feed-in Mode Errors

Fronius CL
138 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
89
EN-US
469
Throttle connected to wrong poles
Cause: Throttle connections IND1 and IND2 incorrect
Remedy: Properly connect throttle connections
Cause: Measurement circuit error in power stage set
Remedy: Replace power stage set
Cause: L and N reversed in the connection area
Remedy: Check AC cabling
473
Error while allocating an AC phase to the power stage set
Cause: One-time occurrence
Remedy: Remedied automatically
Cause: Incorrect DIP switch position on the power stage set
Remedy: Check dip switch on the power stage set
Cause: No AC power supply to the power stage set
Remedy: Check AC fuse in the power stage set
Cause: Faulty ribbon cable connection between the power stage set and the Snow-
ball PC board
Remedy: Check ribbon cable and replace if necessary
474
100 kohm solar module grounding measurement detected an error between the DC+ or
DC- to the ground
Cause: Insulation fault in solar module
Remedy: Check lines and solar modules
Cause: 100 kohm module grounding defective
Remedy: Check and, if necessary, replace the 100 kohm module grounding
Cause: Measurement error in power stage set
Remedy: Replace power stage set
Service class 5 Messages of this class generally do not prevent the feed-in mode of the inverter. They will
be displayed until the message is acknowledged by pressing a key on the inverter (during
this period, the inverter continues feed-in mode).