Calibrating the
empty state
1
Drain the parting agent container until
the parting agent level is at least 20
mm (0.787 in.) below the sensor
2
Establish a power supply to the sensor
3
Press the "OUT OFF" button for
between 2 and 6 seconds
- The LED on the sensor flashes
slowly
- After releasing the "OUT OFF"
button the LED goes out - the
sensor has detected a low fluid
level
Calibrating the
full state
1
Fill the parting agent container with
parting agent
2
Press the "OUT OFF" button for at
least 6 seconds
- The sensor LED flashes slowly at
first, then more rapidly after 6
seconds
- After releasing the "OUT OFF"
button the LED goes out - the
sensor has detected a high fluid
level